Address
Hawker Business Park
Melton Road
Melton Road
Loughborough
LE12 5TQ
Opening Hours
Today
08:30-17:00
View All Hours
Sunday
Closed
Monday
08:30-17:00
Tuesday
08:30-17:00
Wednesday
08:30-17:00
Thursday
08:30-17:00
Friday
08:30-17:00
Saturday
Closed
Trade Supplier of Professional Fire Detection Equipment
About FireAgent
Spec it, quote it, done — fire-detection supply, built like an ERP.Not just a shop
- Every part backed by its real datasheet, specs and compatibility — not just a price.
- Live stock and trade pricing, kept in sync from the manufacturers.
- Build a priced quote in seconds
- paste a parts list or pick from the catalogue.
Gent by Honeywell
Gent by Honeywell covers the Vigilon and Nano addressable fire alarm range, including Nano single-loop, Vigilon Compact, Compact Plus and Vigilon Plus control panels (1 to 6 loop variants), with loop cards, network cards and battery enclosures. It also includes a wide range of spares and accessories such as flush surrounds and mounting kits, replacement PCBs, PSUs, doors, ribbon cables, fixings, thermal printers and paper.
Morley Addressable Panels
Morley Addressable Panels covers the Morley-IAS Max range of single, two, four and expandable eight-loop control panels (networkable and non-networkable) supporting Morley-IAS, System Sensor and Apollo protocols. It also includes bezels, loop cards, communication dongles, main control boards with LCD displays by region, user terminal boards, PSUs, ribbon cable kits and battery cables.
Ancillaries
Ancillaries covers supporting fire-system hardware including magnet door holders (24V DC and 240V AC, floor- and surface-mounted), door holder floor plates and spare plate assemblies, transformer rectifiers (24VDC 2.0A and 4.0A), EN54-4 power supplies (24VDC 2.5amp and 5amp), and a lockable enclosure for storage of site documentation.
Batteries
Batteries holds flame-retardant backup batteries for fire alarm and VA/PA systems, including Power Sonic, Powersonic and YUASA NP cells ranging from 1.2Ah to 38Ah in 6V and 12V, plus larger 12V 65Ah, 105Ah and 150Ah units for VA/PA emergency PSUs. Many are specified for particular panels such as Vigilon, Sentri, Xenex, FP595, Horizon, DXc and ZXSe.
BS8629 Evacuation Alert System
BS8629 Evacuation Alert System covers the Evac Smart EACIE range of loop-based BS8629 evacuation alert panels in 12, 24, 36 and 48 zone variants, each requiring a FACP and supplied with battery but excluding the Gerda box. These products are listed as coming soon in 2026; contact sales support for more information.
Conventional
Conventional covers non-addressable fire alarm equipment, including 2, 4 and 8 zone conventional control panels (such as the HRZ-e range) and repeat indicators, plus detection devices like optical smoke and fixed heat detectors and their bases. It also includes input/output and sounder modules, end-of-line monitors, fire/fault relay units, and a range of spares such as mouldings, cover plates, flush plates, keys and installation kits.
Flame Detection
Flame Detection holds optical flame detectors using IR2/UV, triple IR, UV, UV/IR and IR3 technologies (including FS20X, FS24X and FSL100 ranges) in aluminium and stainless steel for zoned hazardous and safe areas. It also covers accessories such as test lamps, swivel mounts, sunshields, airshields, electronics and diagnostic modules, plus replacement bulbs, batteries and charger kits.
Graphics & Workstation
Graphics & Workstation covers the WINMAG 8 graphics management software, including base packages and additional data-point licences (from 500 up to 50,000 points), client licences in single and multi-seat packs, version upgrades, and option modules for Gent and Notifier fire systems, Variodyn D1 and multi-monitor support.
Honeywell CLSS
Honeywell CLSS covers the Connected Life Safety Services cloud platform, including the fixed CLSS Gateway (Ethernet and Wi-Fi), GSM module, CLSS bar codes, and ready-made Vigilon and Morley DXc connection bundles. It also includes yearly gateway connection fees for single panels and networks, facility manager and VESDA licences, and Self-Test licences in 1 to 14 year terms.
Intrinsically Safe Gent
Intrinsically Safe Gent covers ATEX-approved detection and alarm devices for hazardous areas, including intrinsically safe heat, optical smoke and dual-angle optical heat detectors, indoor and outdoor call points, a monitored Banshee Excel sounder and an IS Flashdome visual indicating device. It also includes Z-System Zener barriers for intrinsically safe detectors and AV devices.
Li-ion Tamer
Li-ion Tamer covers lithium-ion battery off-gas monitoring equipment, comprising a multi-output system, a UL interface module and a GEN2+ monitoring sensor.
Gallery
News
We supply Gent S-Quad Self-Test detectors for app-controlled functional testing, with heat, optical and alarm-output options for specifiers and maintenance contractors.
TESTING ACCESS AND MAINTENANCE
We stock Gent’s S-Quad Self-Test range, known as S4T, which brings functional sensor testing into the detector and connects it to the Honeywell Connected Life Safety Services (CLSS) app. For maintenance contractors, this reduces the need to reach each detector with test equipment when testing its sensing elements. The engineer can select an individual device or groups by zone, loop or panel through the app. Devices and zones outside the test remain active and able to detect a fire. The range includes heat, optical-and-heat and dual-optical-and-heat detectors, with sounder, voice and visual alarm combinations.
HEAT AND SMOKE RESPONSE
The heat test warms the thermistor, the temperature-sensing element, and checks its response to that rise in temperature. On models with optical sensing, the detector generates aerosol inside the device and directs it into the sensing chamber to test the optical response. A fan then clears the aerosol through the smoke entry points, providing a check for masking or obstruction, including a dust cover left in place. On the dual optical models, both optical channels are checked as part of this process. Heat-only versions test their heat sensor and have no optical smoke-sensing element. During normal operation, regular detector readings also build a background performance record, and the panel compares measurements with patterns and rules when assessing a possible fire.
INSPECTION AND RECORDS
Functional testing sits alongside a visual inspection, with Bluetooth Low Energy built into each S4T device to support the engineer’s visit. The Bluetooth connection helps identify the detector and verifies that the engineer has been within visual inspection range. The app provides device information including its number, label, zone description and detector type. CLSS reports distinguish between tests performed manually and through Self-Test, and record whether visual inspection used Bluetooth. They also capture corrective actions, while CLSS records the number of self-tests used by each device. These records bring the testing method and inspection details together for the maintenance contractor.
PANEL COMPATIBILITY AND STANDARD S-QUAD
S4T adds a self-test module and Bluetooth beacon to the standard detector platform and retains compatibility with the S4-700 base. Self-Test operates on Vigilon Plus and Compact Plus systems with compatible firmware, SD-card MCC or MCB hardware and VIGPLUS-LPC-EN loop cards. Nano is not supported. Testing also needs a CLSS gateway for each network domain, the mobile app and an active Self-Test licence. For refurbishment specifications, S4T devices can share a loop with older devices supported by the VIGPLUS-LPC-EN card.
DETECTION AND ALARM OPTIONS
We supply the S4T-711 as a dual optical and heat detector without an integral sounder or visual alarm. Its optical chamber measures at two angles, allowing the panel to compare the readings and distinguish certain smoke aerosols from dust or steam. The S4T-711-V-VAD-HPR combines dual optical and heat detection with a voice sounder and a High Power red visual alarm device (VAD). That provides sensing, spoken messages and visual warning in one head. Its default spoken messages cover evacuation, waiting for further instructions, a system test and fire evacuation, with an attention tone before speech. The wider range also offers heat-only and optical-and-heat models with tone sounders.
ORDER FROM FIREAGENT
Order from our FireAgent S4T-711 — https://fireagent.co.uk/product/s4t-711 page for dual optical and heat detection, or our FireAgent S4T-711-V-VAD-HPR — https://fireagent.co.uk/product/s4t-711-v-vad-hpr page for the version with a voice sounder and High Power red VAD. Our FireAgent S4 Self Test Detectors — https://fireagent.co.uk/products/gent-by-honeywell/s4-self-test-detectors category brings the range together, with options to add products to a basket or quote.
TESTING ACCESS AND MAINTENANCE
We stock Gent’s S-Quad Self-Test range, known as S4T, which brings functional sensor testing into the detector and connects it to the Honeywell Connected Life Safety Services (CLSS) app. For maintenance contractors, this reduces the need to reach each detector with test equipment when testing its sensing elements. The engineer can select an individual device or groups by zone, loop or panel through the app. Devices and zones outside the test remain active and able to detect a fire. The range includes heat, optical-and-heat and dual-optical-and-heat detectors, with sounder, voice and visual alarm combinations.
HEAT AND SMOKE RESPONSE
The heat test warms the thermistor, the temperature-sensing element, and checks its response to that rise in temperature. On models with optical sensing, the detector generates aerosol inside the device and directs it into the sensing chamber to test the optical response. A fan then clears the aerosol through the smoke entry points, providing a check for masking or obstruction, including a dust cover left in place. On the dual optical models, both optical channels are checked as part of this process. Heat-only versions test their heat sensor and have no optical smoke-sensing element. During normal operation, regular detector readings also build a background performance record, and the panel compares measurements with patterns and rules when assessing a possible fire.
INSPECTION AND RECORDS
Functional testing sits alongside a visual inspection, with Bluetooth Low Energy built into each S4T device to support the engineer’s visit. The Bluetooth connection helps identify the detector and verifies that the engineer has been within visual inspection range. The app provides device information including its number, label, zone description and detector type. CLSS reports distinguish between tests performed manually and through Self-Test, and record whether visual inspection used Bluetooth. They also capture corrective actions, while CLSS records the number of self-tests used by each device. These records bring the testing method and inspection details together for the maintenance contractor.
PANEL COMPATIBILITY AND STANDARD S-QUAD
S4T adds a self-test module and Bluetooth beacon to the standard detector platform and retains compatibility with the S4-700 base. Self-Test operates on Vigilon Plus and Compact Plus systems with compatible firmware, SD-card MCC or MCB hardware and VIGPLUS-LPC-EN loop cards. Nano is not supported. Testing also needs a CLSS gateway for each network domain, the mobile app and an active Self-Test licence. For refurbishment specifications, S4T devices can share a loop with older devices supported by the VIGPLUS-LPC-EN card.
DETECTION AND ALARM OPTIONS
We supply the S4T-711 as a dual optical and heat detector without an integral sounder or visual alarm. Its optical chamber measures at two angles, allowing the panel to compare the readings and distinguish certain smoke aerosols from dust or steam. The S4T-711-V-VAD-HPR combines dual optical and heat detection with a voice sounder and a High Power red visual alarm device (VAD). That provides sensing, spoken messages and visual warning in one head. Its default spoken messages cover evacuation, waiting for further instructions, a system test and fire evacuation, with an attention tone before speech. The wider range also offers heat-only and optical-and-heat models with tone sounders.
ORDER FROM FIREAGENT
Order from our FireAgent S4T-711 — https://fireagent.co.uk/product/s4t-711 page for dual optical and heat detection, or our FireAgent S4T-711-V-VAD-HPR — https://fireagent.co.uk/product/s4t-711-v-vad-hpr page for the version with a voice sounder and High Power red VAD. Our FireAgent S4 Self Test Detectors — https://fireagent.co.uk/products/gent-by-honeywell/s4-self-test-detectors category brings the range together, with options to add products to a basket or quote.
FireAgent's online catalogue is now live at fireagent.co.uk, built around the way fire alarm engineers actually search: by manufacturer part number. Instead of browsing marketing categories, trade customers can type the code on the box - a Gent S4-711 multisensor, a Morley-IAS loop module, a VESDA aspirating detector, a KAC call point - and land directly on the product with accurate specifications and the current trade price shown ex VAT. The catalogue covers Gent by Honeywell (Vigilon, Vigilon Compact and Nano panels, S-Quad detectors and sounders, S-Cubed sounder beacons and VADs, interfaces and loop cards), the Gent Self-Test range, Morley-IAS panels and devices, VESDA by Xtralis aspirating smoke detection with sampling pipework, and flame-retardant standby batteries. Quantity price breaks apply automatically as order volumes rise, formal written quotations are available for projects and tenders, and many discontinued parts are listed with guidance on current replacements. FireAgent is trade-only and does not install or service systems. The team is available Monday to Friday 08:30-17:00 on 01509 648840 or [email protected], and the company is now also on Facebook (facebook.com/fireagentltd) and Trustpilot.
FireAgent, the trade-only online supplier of fire alarm parts based near Loughborough, now applies quantity price breaks automatically across its catalogue. Engineers and contractors ordering multiple detectors, call points, sounders or interfaces see the discounted trade price on the product page and in the cart, without phoning for a quote. The catalogue is organised by manufacturer part number and covers Gent by Honeywell (Vigilon and Compact panels, S-Quad detectors, S-Cubed sounder VADs), Morley-IAS, VESDA aspirating detection, KAC call points and standby batteries, all EN54-compliant where the standard applies and priced ex VAT. Formal written quotations remain available for larger projects through the website's quote request, and orders can be placed at fireagent.co.uk with support on 01509 648840 during office hours (Mon-Fri 08:30-17:00).
Scotland
UK
Ireland
London